Description
Main Input Voltage | 230 V |
---|---|
Main Output Voltage | 230 V |
Rated power in W | 2700 W |
Rated power in VA | 3000 VA |
Input Connection Type | BS1363A British IEC 60320 C20 Schuko CEE 7 / EU1-16P |
output connection type | 6 IEC 60320 C13 2 IEC 60320 C19 |
number of rack unit | 2U |
Cable length | 1.83 m |
number of cables | 1 |
Battery type | Lead-acid battery |
provided equipment | CD with software Communication cable Documentation CD Installation guide Removable support feet USB cable Warranty card |
product web sub-family | High density |
---|---|
Number of power module free slots | 0 |
Number of power module filled slots | 0 |
Redundant | No |
colour | Black |
---|---|
Height | 43.2 cm |
Width | 8.5 cm |
Depth | 50.8 cm |
Product weight | 22 kg |
Mounting preference | No preference |
Mounting mode | Rack-mounted with kit |
Two post mountable | 0 |
USB compatible | Yes |
Mounting position | Vertical |
network frequency | 40…70 Hz auto-sensing |
---|---|
input voltage limits | 50…150 V 40% load 80…150 V |
Maximum configurable power in W | 2700 W |
---|---|
Harmonic distortion | Less than 2 % |
output frequency | 50/60 Hz +/- 3 Hz sync to mains |
Crest factor | 3 : 1 |
UPS type | Double conversion online |
Wave type | Sine wave |
Bypass type | Built-in bypass |
Maximum configurable power in VA | 3000 VA |
Product certifications | CE EAC |
---|---|
standards | EN/IEC 62040-1:2019/A11:2021 EN/IEC 62040-2:2006/AC:2006 EN/IEC 62040-2:2018 |
Ambient air temperature for operation | 0…40 °C |
---|---|
relative humidity | 0…95 % non-condensing |
Operating altitude | 0…10000 ft |
Ambient air temperature for storage | -20…50 °C |
storage Relative Humidity | Non-condensing 0…95 % |
Storage altitude | 0.00…15240.00 m |
Acoustic level | 50 dBA |
Heat dissipation | 317 Btu/h |
IP degree of protection | IP20 |
Number of battery filled slots | 0 |
---|---|
Number of battery free slots | 0 |
Battery power in VAH | 0 VAh runtime |
Extended runtime | 1 |
Free slots | 0 |
---|---|
Preinstalled device | Network management card 3 with environmental monitoring |
Emergency power off | Yes |
Surge energy rate | 432 J |
---|
Unit Type of Package 1 | PCE |
---|---|
Number of Units in Package 1 | 1 |
Package 1 Height | 24.6 cm |
Package 1 Width | 74.9 cm |
Package 1 Length | 59.4 cm |
Package 1 Weight | 29.6 kg |